Tuesday, August 26, 2008

Pneumatic System Design to Enable Solenoid Valve Online Testing


There are two fails which are widely known in safety system. The first one is called a nuisance fail which does not put the plant system in danger. In fact some nuisance fails will result in spurious trip or unnecessary plant shutdown therefore they cost high as the production stops. The second one is fail danger which is undetected and does not cause a process shutdown. However, if there is an emergency demand, the safety system would be unable to respond properly therefore putting the plant system in danger.

Fail danger frequently occurs on the final elements i.e. actuated valve. One of several causes that make the actuated valve does not work properly upon demand is a failure on its solenoid valve (solenoid valve), either the solenoid coil or the valve. Dirt causes the solenoid valve to stick thus solenoid valve can not change state and unable to respond to emergency shutdown signal.


As mentioned earlier this situation is undetected, however the problem can be resolved by periodic maintenance which does not require shutting down the plant or actuated the main valve.


The following are design and accessories required to enable online testing of solenoid valve.



*Five-way valve shall be key protected to avoid unauthorized testing

During normal plant operation, the solenoid valve is energized, letting the pilot air flow through the solenoid valve, then it passes through the five-way valve and finally pilots the pneumatic pilot valve resulting the air supply is able to reach the actuator. In the meantime, pressure switch is also pressurized by pilot air.


When it is required to test the solenoid valve, five-way valve must be operated by key and hold until test is completed. In this condition, the solenoid valve is bypassed meanwhile the pressure switch is losing its pressure. When the pressure switch reaches its low set point, it signals the control room that the testing is in progress. Now the solenoid valve can be tested without affecting the main valve since the pilot air remains able to reach the pneumatic pilot valve and keeps the main valve in operating condition. By reading pressure gauge, check that solenoid valve is able to respond to emergency shutdown signal and changes its state).
Releasing the key will put the system into normal plant operation

*The purpose of installing a pressure swicth low is to avoid missoperation of
key operated override valve during plant normal operation.
READ MORE >>

Wednesday, August 20, 2008

Completing The Actuated Valve

Actuated valve, also referred as shutdown valve, blowdown valve, on-off valve, mainly comprises of valve body and actuator. Here are several accessories that make actuated valve complete.




1. Solenoid Valve
Comprises of a solenoid and a valve which form is usually a three-way valve. Solenoid converts electrical energy to mechanical energy resulting three-way valve changes its state.

Here is one example how the solenoid valve working in actuated valve that operates in fail safe mode* as shown on above schematic:

Refer to the lower box in schematic when there is no electrical current received by the solenoid (in other word “de-energized”), the spring makes the valve in a state of the inlet port (1a) blocked while the outlet port (1b) connects to the vent port (1c), releasing air inside the actuator to the atmosphere.

If the solenoid is energized by electrical current, it will change the valve state. Refer to the upper box in the schematic, the inlet port (1a) connects to the outlet port (1b) allowing the air supply flowing into the actuator and stroking it, while the vent port (1c) is blocked.


*fail safe mode means that the actuated valve shall bring the system to safe condition when instrument air or electrical starts to fail. Shutdown valve (SDV)shall be closed, or referred as FAIL CLOSE, whereas Blowdown valve shall be opened or referred as FAIL OPEN. More description about fail safe mode, read this post.

In some application where there is no electrical power, pneumatic piloted valve is used in lieu of solenoid valve. It has the same principle as solenoid valve, but the power source is pneumatic instead of electrical.
Commonly used manufacturers: ASCO, VERSA, and BIFOLD.

2. Limit Switch / Position Transmitter
Position transmitter is used to remotely monitor valve opening from the control room. This instrument is attached on the actuator and transmitting analog electrical signals to indicate the exact position of valve opening. Meanwhile limit switch can only provides remote indication of valve status (open or close position) through electrical discreet signal.
Commonly used manufacturers: WESTLOCK

3. Air Filter Regulator
This device filters the air supply and regulates its pressure, resulting clean air supply with constant pressure fed into actuator.
Commonly used manufacturers: FISHER AFSR

4. Quick Exhaust Valve
Quick exhaust valve can increase the reaction of actuator spring when valve is required to fail safe. This is achieved by releasing the exerting fluid inside the actuator into the open line (port 4c), rather than back through the supply line (port 4a) which is more restrictive as it has to pass flow regulator valve and solenoid valve.
Commonly used manufacturers: VERSA

5. Flow Regulator Valve
To achieve the required closing and/or opening time of actuated valve
i. Uni directional flow regulator
This valve regulates flowrate of air supply in one direction only, while it doesn’t regulate the flowrate of air supply from other directions hence full flow will be passed through. It is used to set the opening time of SDV or closing time of BDV. During start-up the actuator is stroked with rate of movement depends on air supply flowrate flowing into the actuator. FRV will restrict the flow from (5.ia) to (5.ib) resulting the flow rate of air supply into the actuator decreases so that the actuated valve will move slower. If the actuated valve is required to fail safe, the air supply shall be vented from the solenoid vent port (1c). The uni-direction FRV will keep full flow from (5.ib) to (5.ia).
ii. Bidirectional flow regulator
Unlike uni-directional FRV, bidirectional FRV applies restriction to both directions. Installing this FRV will set the time required by the actuated valve to change its state to safe position.

6. Check Valve
It allows flow from one direction only i.e from (6a) to (6b). Commonly check valve is used to protect the upstream equipment from back flow.

7. Bug Screen/Silencer/Dust Excluder
This prevents bug or dust entering the pneumatic system from ports open to the atmosphere.
READ MORE >>

.


Blogspot Template by Isnaini Dot Com